A differential pressure transmitter measures the difference in pressure between two points and converts it to a standard 4-20 mA signal. Plants use these transmitters to measure liquid and gas flow, level and condition of filters.
If you are a process engineer or EPC buyer, this guide explains how a differential pressure transmitter works and when it is used to help you determine if it should be specified in your design.
Differential pressure transmitters measure and output a signal representative of the difference in pressure between the high and low pressure ports. Recent designs employ thin diaphragms of a capacitive design.
Here is what happens inside, step by step:
Capacitance depends inversely on the distance between plates. So the low-pressure side capacitance rises while the high-pressure side falls.
They also have an isolating diaphragm, which is filled with a fluid, to protect the sensor from over pressure. The combination of these two diaphragms gives the instrument a good degree of over range protection. This comes in handy when a valve suddenly closes or when a process line is surged.
Adding a microprocessor to a differential pressure transmitter allows for linearization and compensation for various temperatures, along with additional diagnostics. The fundamental principle of operation remains the same.
Remote reranging, trimming and verification have removed the need for a technician to climb the pipe rack to make those adjustments. Now you can do it from the comfort of your desk. Not many people would complain about that.
One instrument can be used for measuring flow, level and filter monitoring. The principle of operation remains the same in all the three applications. Only the arrangement of the piping and the associated calculations change.
The differential pressure transmitter measures the pressure drop across an obstruction to flow such as an orifice plate, Venturi, or cone. The control system converts the pressure drop to flow rate.
In a closed tank, the differential pressure transmitter measures the pressure at the bottom of the tank compared to the vapor space above and gives an indication of the level of liquid in the tank.
Two impulse-line setups are common:
A wet leg adds a fixed pressure offset, so you must set zero suppression or elevation in the transmitter. Skip that step, and your level reads wrong from day one.
It is a go-to choice for pressurized vessels, boilers and distillation columns where open-tank tools fall short.
A clean filter has very little pressure drop. A clogged filter has a high pressure drop. Put a differential pressure transmitter across a filter, and you have an obstruction that can be indicated before it effects the process.
Common places you will find this:
The result: maintenance happens when the data says so, not on a guess.
A differential pressure transmitter measures the pressure drop across a restriction, and when applied to flow measurement, flow is proportional to the square root of the pressure drop. This is the DP flow method.
The differential pressure transmitter is the sensor and the restriction is the primary element. Both are required.
Flow is calculated from the pressure difference before and after an orifice plate. The transmitter does that sensing job.
Flow rises with the square root of DP. So a 4:1 turndown in flow becomes a 16:1 turndown in DP. At low flow, the signal gets very small, and accuracy drops.
Missing square-root extraction is a common cause of misread flow totals. Check whether the transmitter or the DCS does the extraction. Do not let both do it, or neither.
ISO 5167-2:2022 covers orifice plates, nozzles and Venturi tubes in pipes larger than 50 mm. Following it keeps flow uncertainty predictable and calculable. Actual uncertainty depends on the primary element, installation and fluid data.
A multivariable transmitter measures differential pressure, static pressure and process temperature in one device. It then calculates compensated mass flow on board.
Gas and steam density changes with pressure and temperature, so a plain DP signal drifts. A multivariable unit fixes that without extra transmitters.
For a differential pressure transmitter for temperature compensation, note one thing: the DP cell does not sense temperature. A multivariable unit adds a temperature input (usually an RTD) so the calculation can correct for it.
Multivariable features differ from one product to another. Always check the datasheet for supported inputs and calculations.
Start with range, then accuracy, then materials, then output. Get these four right, and most differential pressure transmitter selection problems disappear. Specs differ between products, so always confirm against the datasheet.
Pick a range that encompasses normal operation. A differential pressure transmitter ranges too wide wastes accuracy. A transmitter ranged too narrow clips during process upsets.
Accuracy is application dependent and varies by manufacturer. It generally worsens as the span is reduced. Always check the datasheet to get the exact figure at the span of interest.
A remote diaphragm seal is used to protect the transmitter from hot, corrosive, viscous and clogging process fluids. A capillary line carries the process fluid to the transmitter cell.
Use one when:
Trade-off: seals add cost, so size them with your supplier.
The diaphragm is in contact with your process. Diaphragms are typically made of stainless steel and are suitable for water and most hydrocarbons. Other media require the use of remote diaphragm seals. Using the wrong diaphragm material can turn your expensive transmitter into an expensive paperweight quickly.
4–20 mA is the analogue backbone of most plants. HART puts digital process data on top of that signal, so you keep the same two wires and gain diagnostics and remote configuration.
Fieldbus options exist too. Many models also support PROFIBUS PA and FOUNDATION Fieldbus alongside HART.
A standard pressure transmitter reads one pressure value against a reference. A differential pressure transmitter reads the difference between two pressure values. Buy the wrong one and your flow or level measurement is worthless.
Most field problems come from the impulse lines, not the sensor. Watch for these:
A good DP transmitter supplier will share a simple commissioning checklist. Ask for it.
Look past the price. A good DP transmitter supplier gives you:
For EPC projects, ask one more question: can they supply the transmitter, manifold and primary element as a matched package? It cuts interface headaches.
Almost every process plant has a few, from a basic pressure transmitter to a smart digital differential pressure transmitter. Sectors that rely on a DP transmitter:
1. What is the use of a DP transmitter?
To measure differences in pressure and hence level, flow and pressure drop across filters.
2. What are the major differences between a differential pressure transmitter and a pressure transmitter?
A pressure transmitter measures pressure with respect to a reference. A differential pressure transmitter measures the difference between two pressures.
3. What kind of signal does a differential pressure transmitter give?
Most differential pressure transmitters give a 4 to 20 mA signal with HART communication over the same signal.
4. Can a DP transmitter measure flow without an orifice plate?
No. A differential pressure transmitter measures the difference in pressure across an element that creates the pressure drop.
5. Why are differential pressure signals transmitted after a square root extraction?
Due to the non-linear relationship between differential pressure and flow.
6. How do I select the range of a differential pressure transmitter?
Select the range of the transmitter based on the maximum differential pressure expected, and add a safety factor.
Need to specify your DP transmitter? Burak will provide you a quote based on your range, media, and output requirements.
You can also check out our differential pressure flow meter guide to learn about designs such as orifice, Venturi, nozzle and V-Cone.
Subscribe to our newsletter for updates!